Instruction & Technical Manual | 37
Standard pressure dewpoint -40ºC (-40°F)
-70ºC (-100°F) with application of
flow correction factor
Min working pressure 4 barg (58 psig)
Max working pressure 16 barg (232 psig)
Electric controls 12VDC to 24VDC, 100VAC to 240VAC
Min inlet temperature 1.5ºC (35ºF)
Max inlet temperature 50ºC (122ºF)
Min ambient temperature 5ºC (41ºF)
Note: The temperature and pressure correction factors (below) should be applied to the above flow rates to suit the
application and ensure dryer performance. All flow rates are based on 7.0 barg (100 psig) and 35°C (95°F) at the dryer
inlet.
*Always use the pressure correction factor (PCF) closest to the actual inlet pressure condition
Operating pressure barg (psig) 4 (58) 5 (72) 6 (87) 7 (100) 8 (116) 9 (130) 10 (145) 11 (160) 12 (174) 13 (189) 14 (203) 15 (218) 16 (232)
Pressure correction factor (PCF)* 0.62 0.75 0.87 1 1.12 1.25 1.37 1.5 1.62 1.75 1.87 2.0 2.12
Temperature °C (°F) 20 (68) 25 (77) 30 (86) 35 (95) 40 (104) 45 (113) 50 (122)
Temperature correction factor (TCF) 1.07 1.06 1.04 1.00 0.93 0.78 0.64
Dewpoint °C (°F ) -40 (-40) -70 (-100)
Dewpoint correction factor (DCF) 1 0.7
SPECIFICATION
13. Dryer Sizing Table
B
A
C
DRYER PIPE INLET FLOW RATE DIMENSION (mm) WEIGHT DIMENSION (inch)
MODEL SIZE Nm
3
/h SCFM* A B C Kg lb A B C
AC119
3
/
8
"
10.2 6 504 281 92 14 31 20 11 3.6
AC122
3
/
8
"
13.6 8 565 281 92 15 33 22 11 3.6
AC126
3
/
8
"
17.0 10 635 281 92 16.5 36 25 11 3.6
AC136
3
/
8
"
25.5 15 815 281 92 19.5 43 32 11 3.6
AC148
1
/
2
"
37.4 22 1065 281 92 24 53 42 11 3.6
AC171
1
/
2
"
56.1 33 1460 281 92 31 68 57.5 11 3.6
AC191
1
/
2
"
74.8 44 1065 281 184 47 104 42 11 7.25
AC196
3
/
4
"
112.2 66 1460 281 184 61 135 57.5 11 7.25